Display and controls

Non-programmable thermostat for electric floor heating
TH1300

Display and controls

Non-programmable thermostat for electric floor heating
TH1300

Affichage secondaire : Température extérieure (Out)
Température ambiante
Indicateur de chauffage

Changing settings from the device

To change the temperature settings or the control cycle, you must:

1

Lower the setpoint temperature to its minimum and keep the    button pressed for 10 seconds to access the menu.

2

Press the  or  buttons to change the setting.

3

Press the  and   buttons simultaneously to select the next parameter. Continue to press until the end of the list to exit the menu.

Temperature regulation modes

Mode A : Regulates the ambient temperature with the possibility to limit floor temperature by means of an external temperature sensor.

Mode F : Regulates the floor’s temperature by means of an external temperature sensor with the possibility to li mit ambient temperature.

Advanced settings

#

NameParameters & settings
1Temp

Temperature format

°C or °F – (default: °C)

2Control

Control mode

A (Air), F (Floor) – (default: F)

3Aux

Assignment of auxiliary output

Shrt, Long, Slave – (default: Slave) (1)

4Min

Minimum setpoint

5 °C to 30 °C – (default: 5 °C)

5Max

Maximum setpoint

5 °C to 30 °C – (default: 30 °C)

 

6Min Floor

Minimum floor temperature

5 °C to 30 °C – (default: OFF) (2)

7Max Floor

Maximum floor temperature

5 °C to 30 °C – (default: OFF) (2)

8Max Air

Maximum ambient temperature

5 °C to 30 °C – (default: OFF) (3)

9Sens

Floor sensor

10K ou 12K – (default: 10K)

10BL

Backlight control

ON or OFF – (default: ON)

11Load

Load power

0 W tp 3600 W (4)

Mode A seulement

1) Assigning the auxiliary output

The thermostat provides an auxiliary output that has three functions that are set from the user settings.


Shrt Function: Short cycle auxiliary output (15 seconds).
Used for a heater controlled through an electronic relay (SSR).

Long Function: Long cycle auxiliary output (15 minutes).
Used for a heater controlled through an electromechanical relay
or equipped with a fan.

Slave Function: Auxiliary output to connect several heating floors (TR1310 sold separately).

In A mode the thermostat controls the ambient temperature with the floor. Once the floor temperature has reached its limit, if the desired ambient temperature is not reached, the auxiliary output activates the heating device to reach the set temperature. (The auxiliary output acts as a second heating stage.)

2) Maximum floor temperature limit

The thermostat limits floor heating ta the set temperature ta ensure it does not exceed the selected limit. Ideal for protecting engineered wood floors. (Verify with your flooring manufacturer to determine heat limit.)

Mode F seulement

3) Limite maximale de la température (ambiante)

The thermostat limits floor heating to ensure that the ambient temperature does not exceed the selected limit.

Mode A et F

4) Load power

The thermostat is equipped with a sensor that can read the load in watts connected to the thermostat.