Changing settings from the device

To change the temperature settings or the control cycle, you must:

1

Lower the setpoint temperature to its minimum and keep the  button pressed for 10 seconds to access the menu.

2

Press the  or  buttons to change the setting.

3

Press the  and  buttons simultaneously to select the next parameter. Continue to press until the end of the list to exit the menu.

 

The TH1400WF thermostat offers 2 temperature regulation modes:

A mode (default)

Regulates ambient temperature with the possibility to limit floor temperature by means of an external temperature sensor.

F mode

Regulates the floor temperature by means of an external temperature sensor with the possibility to limit ambient temperature.

Settings that can be changed from the device

#

NameParameters & settingsDisplay
1Temp

Temperature format

°C or °F – (default: °C)

°C

2Control

Control mode of the thermostat

A (Air), F (Floor) – (default: Air)

 A

3Max Air

Maximum ambient temperature limit

5 °C to 36 °C – (default: OFF)

 OFF

4Max Floor

Maximum floor temperature limit

7 °C to 36 °C – (default: OFF) 

 OFF

5Min Floor

Minimum floor temperature limit

5 °C to 36 °C – (default: OFF)

 OFF

6Cyc

Cycle length / Main output

15 sec, 5 min, 10 min, 15 min, 20 min, 25 min, 30 min – (default: 15 min) 

 15

7Aux Cyc

Cycle length / Auxiliary output

OFF, 15 sec, 5 min, 10 min, 15 min, 20 min, 25 min, 30 min – (default: OFF) 

OFF 

8Sens

Floor sensor

10 K or 12 K – (default: 10 K)

 10

PE

Circulator pump’s anti-seizure

ON or OFF – (default: OFF)

OFF 

3) Maximum limit of the ambient temperature (F mode)

Thermostat limits floor heating so as not to exceed the set ambient temperature limit.

4) Maximum floor temperature limit (A mode)

The thermostat limits floor heating to the set temperature to ensure it does not exceed the selected limit.

This parameter is ideal for protecting engineered wood floors. (Verify with your flooring manufacturer to determine heat limit.)

This parameter is only usable when a floor sensor is connected to the thermostat.

5) Minimum floor temperature limit (A mode)

The thermostat limits the minimum temperature of the floor in order to keep it at a comfortable temperature.

This parameter can only be used when a floor sensor is connected to the thermostat.

6) 7) Main and auxiliary output cycle length

The thermostat has a main and an auxiliary output. Select the appropriate cycle length based on your heating system. The selection of an inappropriate cycle length may damage your unit.

Minimum cycle length (min)0.1551015202530
Convector or baseboard heater activated by an electronic relay (SSR)x      
Fan-forced convector activated by an electronic relay (SSR) xx    
Fan-forced convector or baseboard heater activated by a mechanical relay  xx   
Hydronic heating pump system   xxxx
Furnace   xxxx

9) Circulator pump's anti-seizure

When the thermostat is not heating for an extended period, this parameter will activate the main output during 1 minute every 24 hours to ensure the hydronic system pump does not seize.