Error code
OL
Issue
The overload protection of the product is activated. The connected electrical load is too high.
Verification
Make sure that the electrical load connected to the thermostat is equal to or less than its technical limitation.
Line voltage thermostat | Maximum load @ 120VAC | Maximum load @ 240VAC |
| TH1120RF-3000 | 1500 W | 3000 W |
| TH1120RF-4000 | 2000 W | 4000 W |
| TH1121RF-3000 | 1500 W | 3000 W |
| TH1121RF-4000 | 2000 W | 4000 W |
| TH1123ZB | 1500 W | 3000 W |
| TH1124ZB | 2000 W | 4000 W |
| TH1123WF | 1500 W | 3000 W |
| TH1124WF | 2000 W | 4000 W |
| TH1500RF | 1800 W | 3600 W |
| TH1500ZB | 1800 W | 3600 W |
Solution
Perform a reset of the circuit breaker.
- Find the circuit breaker connected to the unit.
- Disable it.
- Wait about 30 seconds.
- Reactivate the circuit breaker
Was this article helpful to you?
- Yes
- No
Recherchez d'autres sujets
[ivory-search id="43527" title="Thermostats"]
Tagged Error code