Error code
OL2
Issue
The overload protection of the product is activated, or the internal temperature of the product is too high.
Verification
Make sure that the electrical load connected to the thermostat is equal to or less than its technical limitation.
Line voltage thermostat | Maximum load @ 120VAC | Maximum load @ 240VAC |
| TH1120RF-3000 | 1500 W | 3000 W |
| TH1120RF-4000 | 2000 W | 4000 W |
| TH1121RF-3000 | 1500 W | 3000 W |
| TH1121RF-4000 | 2000 W | 4000 W |
| TH1123ZB | 1500 W | 3000 W |
| TH1124ZB | 2000 W | 4000 W |
| TH1123WF | 1500 W | 3000 W |
| TH1124WF | 2000 W | 4000 W |
| TH1500RF | 1800 W | 3600 W |
| TH1500ZB | 1800 W | 3600 W |
Check that no external source influences the temperature of the thermostat.
Solution
Perform a reset of the circuit breaker.
- Find the circuit breaker connected to the unit.
- Disable it.
- Wait about 30 seconds.
- Reactivate the circuit breaker