Display and controls

Smart low voltage thermostat
TH1400RF

Display and controls

Smart low voltage thermostat
TH1400RF

État de connexion avec la passerelle
Heure
Affichage secondaire : Température extérieure (Out)
Température ambiante

Changing settings from the device

To change the temperature settings or the control cycle, you must:

1

Lower the setpoint temperature to its minimum and keep the button pressed for 10 seconds to access the menu.

2

Press the  or  buttons to change the setting.

3

Press the  and  buttons simultaneously to select the next parameter. Continue to press until the end of the list to exit the menu.

Settings that can be changed from the device

#

NameParameters & settings
1Temp

Temperature format

°C or °F – (default: °C)

2Control

Control mode of thermostat

A (Air), F (Floor) – (default: A)

3Cyc

Cycle length / Main output

15 sec, 5 min, 10 min, 15 min, 20 min, 25 min, 30 min – (default: 15 min) (1)

4Aux Cyc

Cycle length / Auxiliary output

OFF, 15 sec, 5 min, 10 min, 15 min, 20 min, 25 min, 30 min – (default: OFF) (1)

5Min On

Minimum time On 

0 sec, 30 sec, 1 min, 2 min, 3 min, 4 min, 5 min – (default: 0 sec) (2)

6Min Off

Minimum time OFF

0 sec, 30 sec, 1 min, 2 min, 3 min, 4 min, 5 min – (default: 0 sec) (3)

7Min

Minimum setpoint

5 °C to 30 °C – (default: 5 °C)

8Max

Maximum setpoint

5 °C to 30 °C – (default: 30 °C)

 

9Min Floor

Minimum floor temperature limit

5 °C to 30 °C – (default: OFF)

10Max Floor

Maximum floor temperature limit

5 °C to 30 °C – (default: OFF) (4)

11Max Air

Maximum ambient temperature limit

5 °C to 30 °C – (default: OFF)

12Sens

Floor sensor

10 K or 12 K – (default: 10 K)

13bL

Backlight control

ON/OFF – (default : ON)

14PE

Circulator pump’s anti-seizure

ON or OFF – (default: OFF) (5)

1) Longueur du cycle de la sortie principale et auxiliaire

The thermostat has a main and an auxiliary output. Select the appropriate cycle length based on your heating system. The selection of an inappropriate cycle length may damage your unit.

Minimum cycle length (min)0.1551015202530
Convector or baseboard heater activated by an electronic relay (SSR)x      
Fan-forced convector activated by an electronic relay (SSR) xx    
Fan-forced convector or baseboard heater activated by a mechanical relay  xx   
Hydronic heating pump system   xxxx
Furnace   xxxx

2) Minimum time ON

This parameter determines the minimum operation time of the thermostat before it turns OFF.  This ensures heating is not running for a shorter time period than the starting of the heating system.

Note: It is recommended to select the same duration as the starting time of the heating system, without exceeding 20% of the chosen cycle length.

3) Minimum time OFF

This parameter determines the minimum period for which the thermostat must stay OFF before its output is reactivated.

4) Maximum floor temperaure limit (Mode A)

The thermostat limits floor heating to the set temperature to ensure it does not exceed the selected limit. This parameter is ideal for protection engineered wood flooring. (Verify with your flooring manufacturer to determine heat limit.)

This parameter is only available when a floor sensor is connected to the thermostat.

5) Circulator pump's anti-seizure

When the thermostat is not heating for an extended period, this parameter will activate the main output for 1 minute every 24 hours to ensure the hydronic system pump does not seize.

Rechercher

Now add your smart low voltage thermostat to your gateway

You can now move on to configuring your thermostat with your preferred gateway to get more features.

You will find below the most common issues you may encounter.

If you still need help, contact Sinopé technical support.